Dexter error codes

Dexter T-Series vended washers (T-300, T-350, T-400, T-450, T-600, T-650, T-900, T-950, T-1200) and A-Series washers use a main controller that talks to a variable frequency drive (VFD). Fault codes appear on the front display as F1, F2 and so on. Many faults also leave a separate code on the VFD itself, so always look at the drive display before cutting power.

Important: record the VFD fault code before you turn the machine off. When you do power down, leave it off for about three minutes so the drive fully resets. Turning it back on too quickly can cause F13 or F21.

Covers: T-Series and A-Series vended and OPL washer-extractors with VFD drives; T-30x2, T-50x2 and Express stack dryers.
Based on: Dexter WCAD-Series vended washer troubleshooting and fault codes, A-Series machine fault code errors, and T-30x2 Express dryer troubleshooting.

Washer fault codes

Door failed to lock or stay locked

The door did not close and lock, or it unlocked during the cycle.

  • Listen for the door solenoid engaging when the cycle starts.
  • Check the door adjustment and that the handle closes fully.
  • Technician: check door/lock switch wiring and the connector at the controller, then adjust the lock mechanism.

Did not fill within 7 minutes

The tub did not reach water level in about 7 minutes. The wash continues; the code flashes and clears at the end of the cycle.

  • Make sure water is on and pressure is adequate.
  • Clean inlet screens.
  • Check that the drain valve is closing. Note: 18 lb washers can show F2 when set to high water level.

Controller memory error

The controller's memory checksum is wrong.

  • Technician: try a soft reset of the controller. If it returns, the controller board needs replacement.

Controller communication error

Internal communication problem in the washer controller.

  • Technician: check the data cable for side tension at both ends and the controller connections. Replace the controller if it returns.

Pressure switch error (OPL)

The high-level sensor reads full while the low-level reads empty.

  • Technician: test the pressure switch contacts and the harness connector for pushed-out pins.

Wrong drive size or setting

The controller and drive do not match the machine size, often after a board or drive was swapped.

  • Technician: confirm the correct VFD horsepower and harness for this model, then soft reset by holding the program button at power-up.

Did not drain within 7 minutes

The tub did not empty in about 7 minutes. A slow drain is a common cause.

  • Clear the drain valve and drain line.
  • Technician: check the pressure switch tube for blockage and the pressure switch itself.

Did not reach spin speed within 150 seconds

The basket did not reach the target spin frequency.

  • Make sure the basket turns freely by hand with power off.
  • Technician: check the drive enable signal, door switch, braking resistors and the VFD.

Did not stop within 150 seconds after spin

The basket kept turning too long after the spin ended.

  • Technician: measure the braking resistors and their wiring to the drive; check drive programming.

Internal controller or drive error

An internal error in the controller (F12) or the drive (F20).

  • Power off, wait, power back on. If it reappears, the board or drive needs service.

Drive and controller not communicating

The washer computer and the VFD lost communication.

  • Technician: make sure the data cable is plugged in at both ends with no sideways tension, replace the cable if needed, and inspect the connectors on the controller and drive.

Over-current on drive or motor

The drive saw too much current.

  • Check that the basket turns freely. If not, remove the belt and check whether the motor or the bearings are binding.
  • Technician: check motor leads for shorts and measure the braking resistors.

Drive over-voltage

Internal DC voltage in the VFD is too high, from high supply voltage, electrical noise or the motor feeding voltage back.

  • Technician: measure supply voltage, check braking resistor connections and values. On a 240V high-leg service, disconnecting the high leg or adding a surge suppressor or line choke often cures it.

Drive over-temperature

The VFD's internal temperature is too high.

  • Clean the VFD heatsink fins and cooling fan louvers.
  • Technician: confirm the VFD cooling fan runs once the basket starts turning.

Drive or motor overload

The drive or motor is overloaded.

  • Check that the motor turns freely and the V-belt is not too tight (about 1 inch deflection at center).
  • Technician: check wiring and braking resistors.

Ground fault

The drive detected a ground fault.

  • Technician: check motor and drive wiring for damage and confirm proper grounding.

Low voltage to drive

Supply voltage to the drive is too low.

  • Technician: measure the incoming line voltage and check connections.

Drive data / communication error

Communication noise between controller and drive. Also happens if main power was turned off and on too quickly.

  • Leave power off for three minutes before restarting.
  • Technician: inspect or replace the data cable.

Component added, removed or replaced

Warning codes shown after a VFD, injection relay board or water valve board was replaced, added, removed or has a loose connection.

  • Technician: check the connection, then soft reset the controller so it recognizes the hardware.

Power loss during cycle

Power was lost during the cycle and has returned.

  • Press a temperature selection button to continue the cycle.

Dryer fault codes (T-30x2 / Express)

Shorted temperature sensor

The temperature sensor or its harness is shorted.

  • Technician: check the sensor (about 30,000–60,000 ohms at room temperature) and harness.

Open temperature sensor

The temperature sensor is open or its harness is disconnected.

  • Technician: reconnect or replace the sensor or harness.

Possible grounding problem

The control sees a possible ground issue.

  • Power down and back up, then check the dryer's ground connection.

Control chip problem

An electrical or microchip problem on the control.

  • Remove power for one minute and restore it. If the code returns, replace the controller.

Tumbler turns but no flame

No error code, but the dryer runs cold. Common causes are gas supply, ignition control, spark electrode, gas valve coil or a tripped manual-reset thermostat.

  • Make sure gas is on.
  • Clean lint from around the burner.
  • Technician: check gas pressure with a manometer, 24VAC at the ignition control, spark at the igniter and gas valve coils.

A-Series VFD communication codes (CE)

Drive received a bad command

The variable frequency drive got an illegal command, address or value, or could not carry out the request. Usually a controller or data cable issue.

  • Soft reset the drive and controller.
  • Technician: check the data cable between controller and VFD.

Commands too close together

The time between commands from the controller was too short.

  • Soft reset the drive.
  • Technician: check the controller.

Drive internal checksum error

The VFD found an internal data error.

  • Soft reset; replace the drive if it repeats.

Watchdog timeout

The drive did not receive a command from the controller within about 6 seconds. This often shows when the controller and drive are not communicating.

  • Check the data cable is plugged in at both ends and not pulled sideways.
  • Technician: replace the cable or check the controller.

Frame / message length errors

The message from the controller was garbled, too short, too long or had extra characters. Electrical noise on the data cable is a common cause.

  • Soft reset the drive.
  • Technician: reroute or replace the data cable.

Older stack dryer fault codes

Temperature sensor shorted / open

F1 means the sensor or harness is shorted, F2 means it is open or disconnected.

  • Technician: check the sensor and harness.

Possible grounding problem

Try powering down and back up, then press the programming button to start. If that fails, technicians reset through the handheld programming file or by removing and reinstalling the control battery.

  • Power down and back up.
  • Technician: check grounding and the control battery.

Control microchip problem

Electrical or chip problem on the control board.

  • Remove power for 1 minute and restore.
  • Technician: replace the controller if it repeats.

These explanations are general guidance written by CLS from manufacturer service documentation, and code meanings can vary by control version. Always confirm with the manual for your exact model. Disconnect power (and gas or steam) before opening any panel. Repairs inside the machine should be done by a qualified technician.